The SCAL unit begins the 30 second self-calibration process the first time current is applied in the operating range. The threshold
is then set. Subsequent calibrations may be performed by moving SW1 to the position opposite of its current position with or
without current applied (hands can be safely away from live voltage). Once current begins flowing, or if it already is, the calibration
process will begin. At the end of the 30 seconds, amperage will be read and set as the threshold. SW2 in the ON position provides
a 15% (+/-3%) differential. In the OFF position, it provides a 25% (+/-3%) differential. SW2 can be selected at anytime and does not
affect the threshold setting. Current in-range closes the sensor contact. Current above or below range opens the sensor contact