i-Vu® Building Automation System Carrier® ChillerVu™ - PSM-IO

Item
OPN-PSM-MPCXPE
  • California Prop 65

OVERVIEW

Carrier® ChillerVu™ PSM-IO Module

Carrier ChillerVu is a sophisticated, scalable, native BACnet® control solution for chiller plant control and operation. It consists of a dedicated controller and a library of factory-engineered control programs that are specifically designed to cover the most common chiller plant configurations.

Carrier ChillerVu factory-engineered control programs, with “Plug ‘n Play” support for specific Carrier CCN® PIC chillers, are designed to provide efficient, automatic control over all aspects of a chiller plant, coordinating the control of chillers, pumps and towers into a finely tuned, cohesive system. Whether you have 2 or 20 chillers, the system is able to control Carrier 19, 23, or 30 series chillers (air- or water-cooled). Carrier ChillerVu also supports integration to chiller plant equipment using BACnet, LonWorks® and Modbus® protocols.

FEATURES

System Benefits

  • Chiller Manager – Basic staging for up to 8 chillers, and expandable for larger plants
  • Pump Managers – Primary, secondary, and condenser
    • Coordinated staging for up to 8 headered chilled water pumps in constant or variable primary flow, and in primary/secondary arrangements
    • Coordinated staging for up to 8 headered condenser water pumps in constant flow configurations
  • Tower Manager - Coordinated control of up to 8 open or closed single cooling towers
  • Single Tower - Self-contained tower control programs, including control points for both open and closed tower configurations
  • Single Chiller – Complete control for single chiller systems, includin I/O for a single chiller with dedicated tower and associated pumps
  • Chilled Water Pumps/Basic Arrangements – Single and dual pump control, lead/lag, lead/standby, constant volume, and variable speed
  • Carrier® 23XRV Series Counter Flow (SCF) – This application provides control of two Carrier® 23XRV chiller piped in series/counterflow arrangement. (Certain restrictions apply. Please contact Control Systems Support for additional information regarding SCF applications).

Hardware Features

  • Ethernet Port for LAN, BACnet IP, and/or Modbus TCP/IP communications
  • BACnet Port for BACnet MS/TP communications
  • Supports Auto-discovery of CCN® Devices on a RS-485 port
  • Supports up to 1000 integration points for other plant equipment using BACnet, Modbus® and LonWorks® protocol
  • Supports 20 I/O points directly (12 universal inputs, 8 universal outputs)
  • Supports up to (6) MPC Open XPIO expanders (in any combination) for additional point capacity (164 I/O points total)

Software Features

  • As part of i-Vu Tools, supports library-driven programming using EquipmentBuilder.
  • Supports custom programming using Snap
  • Supports i-Vu Pro user interface for startup & commissioning. NOTE: i-Vu Standard, i-Vu Plus, and Field Assistant are not supported at this time.

California residents please see Proposition 65

Safety Standards
California Prop 65 Yes
Hazardous Material No
Weights and Dimensions
Operating Weight (lbs) 1.7
Exterior Dimensions (D) (inches) 1.437500
Exterior Dimensions (W) (inches) 11.312500
Exterior Dimensions (H) (inches) 7.500000
Shipping Weight (lbs) 1.700000